Technical Manual : 6521355 V1.8.0 07/2014
Installation Data
When installing circulating water pumps or equipment containing them, the following rules
should be applied:
Ensure the system is filled with liquid then vented and the pump primed with water
before running the pump, this is required because the pumped liquid cools the pump
bearings and mechanical seal faces
To avoid cavitation the NPSH (Net Positive Suction Head) incorporating a safety
margin of 0.5m head must be available at the pump inlet during operation
PUMP PACKAGES (OPTIONAL EXTRAS)
A Standard Unit - No Pump
8 Differential Pressure Transducer
Always electrically interlock the operation of the chiller with the pump controls for
safety reasons.
Failure to will invalidate the chiller warranty.
Do not rely solely on the BMS to protect the chiller against low flow conditions.